SOP For monitoring of power consumption is described in this post which you can follow in the section of the General Industry SOP.
OBJECTIVE
To lay down the procedure for monitoring power consumption.
SCOPE
This SOP shall be applicable for monitoring power consumption.
RESPONSIBILITY
Operator
Officer
ACCOUNTABILITY
Head of Engineering
PROCEDURE
Take keys of Kiosk area from security cabin.
Open the window in front of trivector meter and note the meter readings through the glass.
NOTE DOWN FOLLOWING READINGS
- Total Kwh, Total KVAh
- Total KVArh
- KVA M.D. (Zone A, B,C, D)
Take highest KVA M. D. out of A, B, C, D readings.
Enter these reading in M.S.E.B. file in the computer.
Calculate the differences between last readings and today’s readings for Kwh and KVAh.
Use multiplying factor for calculating consumption & recorded demand.
Our multiplying factor (M.F.) is 30 for all parameters.
Calculate power factor, i.e. Total Kwh / Total KVAh.
It should be always between 0.99 and 1.
Close the window in front of trivector meter and then lock the KIOSK Area.
Hand over the keys to security.
Only authorized persons should enter this area since high tension supply is always ON.